Voltage Unbalance Calculator
Enter three phase voltages to compute % unbalance using common industry definitions. Includes Show Work and share links.
How to Use
- Select an input mode (Line-to-Line or Line-to-Neutral).
- Enter three measured voltages (e.g., Vab, Vbc, Vca).
- Choose units (V or kV) and optional rounding.
- Open “Show Work” to see the average, deviations, and formulas.
Show Work (step-by-step)
(max deviation ÷ average) × 100.
Reference
Voltage unbalance is a condition where the three phase voltages are not equal. Higher unbalance can increase motor heating and reduce efficiency.
- Average voltage:
Vavg = (V1 + V2 + V3) / 3 - Max deviation:
Vdev = max(|V1−Vavg|, |V2−Vavg|, |V3−Vavg|) - % Unbalance (common):
% = (Vdev / Vavg) × 100
Note: Different standards may define unbalance differently. This tool includes the most commonly used “max deviation from average” percent form.
FAQ
Should I use line-to-line or line-to-neutral readings?
Use the same type you measured. For typical motor checks, line-to-line readings are common in the field.
What if one reading is missing?
This calculator needs three voltages. If you only have two, re-measure or verify metering.
Is this the same as current unbalance?
No. Current unbalance can be larger than voltage unbalance depending on the load and motor characteristics.
Does this tool diagnose the cause?
No. It quantifies the imbalance. Causes can include utility supply issues, loose connections, single-phasing, or unbalanced loads.